3-5 Receiving and Installation MN715P
Three Phase Wire Size and Protection Devices
Table 3-3 Wire Size and Protection Devices - 3 phase
Control
Control
Rating
Input Fuse Wire Gauge
Input
Volts
Output
HP
Fast Acting
Amps
Time Delay
Amps
AWG mm
2
230 1 6 5 14 2.08
230 1.5 8 7 14 2.08
230 2 12 9 14 2.08
230 3 15 12 14 2.08
230 5 25 20 12 3.31
460 1 3 2.5 14 2.08
460 1.5 4 3.5 14 2.08
460 2 5 4.5 14 2.08
460 3 8 6.3 14 2.08
460 5 12 10 14 2.08
Note: All wire sizes are based on 75°C copper wire, 1% line impedance.
Figure 3-3 Three Phase AC Power and Motor Connections
L1 L2 L3
L1 L2 L3
Earth
AC Motor is not provided with control.
Baldor
Series 15P
Control
Metal conduit should be used to shield output wires
(from T1, T2, T3 of control to T1, T2, T3 of motor).
T1 T2 T3
T1
T2 T3
G
Shield wires inside a metal conduit.
*Optional
Line
Reactor
A1 B1 C1
A2 B2 C2
* Optional components not
provided with 15P Control.
Vista de página 10
1 2 ... 6 7 8 9 10 11 12 13 14 15 16 ... 29 30

Comentários a estes Manuais

Sem comentários